Brand-Gaus Home

Model 621 Temperature Controller

Home  |  Gas Analyzers  |  Temperature Controllers  |  About Us  |  Contact  

Click for close-up images

Model 621: Watlow Series F4 controller and Series 97 limit

The Model 621 Profiling Temperature Controller is a full-featured, industrial quality rackmount temperature controller capable of executing complex temperature profiles (temperature setpoint sequences as a function of time). Up to 30 amps of AC power can be controlled ranging from 100 to 250 VAC.

The Model 621 is an exceptionally user-friendly stand-alone programmable temperature profiler. For more versatility, the Model 621 can be controlled via standard digital communications, and process values or setpoint values can be can be made available through the optional analog output.

Model 621 Base Price: $2450

Optional Features and Pricing

Main Controller Digital Comms  

Includes RS-232 and RS-485 digital communications on the main controller, but only one type is wired to back panel as specified below.

Main controller wired for (specify one only):

 
RS-232 digital comms no charge
RS-485 digital comms* no charge
Main Controller Analog Output  
None no charge
Analog output installed $75
Limit Controller Communications  
None no charge
Analog output $75
RS-232 digital comms $125
RS-485 digital comms* $125
Sensor type  
Common thermocouples (specify K, J, T, E, or N) no charge
Rare-metal/special thermocouples (R/S, B, or C) $25
2-wire 100-Ohm Pt RTD (JIS or DIN) $25
3-wire 100-Ohm Pt RTD (JIS or DIN) $45
AC power input and heater connectors  
NEMA L6-30 (250VAC, 30A, 2-pole plus ground) no charge
NEMA L5-30 (125VAC, 30A, 2-pole plus ground) $40
NEMA L10-30 (125/250VAC, 30A, 2-hot poles, plus neutral) $40

*If RS-485 is ordered for both main and limit controllers, they will be wired to a common 9-pin, D-sub connector.

Real-time Clock and Profile Storage

Up to 256 steps may be programmed and stored in up to 40 user-named profiles. The ability to ramp, soak, autostart, jump and repeat segments offers tremendous flexibility in setting up a wide a variety of complex profiles. A real-time clock allows any profile to be started at any time, which can be specified as a specific date and time, a day of week, or the profile can be repeated daily. The 4x20 alphanumeric display and one-button context-sensitive help greatly simplifies programming and configuration.

Powerful features for demanding process requirements

Advanced features like guaranteed soak band and wait for deviation can be configured so that the controller will wait until the process value has reached and/or has remained within a certain deviation band before clocking soak time or moving on to the next profile step. Up to five sets of PID parameters can be stored allowing a different set to be used for each step of an executing profile.

Dual alarm relays, four event inputs and eight event outputs are available via internal screw terminals that allow additional control of profile execution and the control of other process equipment by the Model 621.

Communications options

Analog and digital communications options can and must be independently specified for the main controller and the limit controller. If RS-485 digital communications is specified for both the main and limit controllers, the two controllers are wired to a common 9-pin D-sub connector. The main and limit controllers are then accessed via address values of 1 and 2 (default values), respectively. If RS-232 is specified for both the main and limit controllers, each controller is wired to its own 9-pin D-sub connector. In this case, a single computer would need to use two serial ports to communicate with both the main and limit controller at the same time.

The Model 621 comes standard with either RS-232 or RS-485 digital communications for the main controller. Note, both RS-232 and RS-485 communications are accessible on the Model 621, but only one is wired to the back panel at the factory. Changing from one interface to the other can easily be done in the field. Additionally, analog output can be ordered for the main controller of the 621 -- while still having the digital communications fully functional. Analog input for remote setpoint adjustment is not available on the Model 621. The limit can be ordered with RS-232, RS-485, or analog output.

Communications Protocol

Both the Model 521 and the Model 621 temperature controllers use the industry standard MODBUS RTU messaging protocol over either RS-232 or RS-485 interfaces. MODBUS provides a robust communications protocol by incorporating verified message reception and CRC (checksum) error detection. MODBUS is used by several of the most popular industrial PLC's.

Analog Input and Analog Output Ranges

Analog input and analog output support all the common industrial DC ranges: 0-5V, 0-10V, 1-5V, 4-20mA, and 0-20mA. The main and limit controllers can independently be configured to map the full resolution of the analog range to the desired range of temperatures.

Specifications

  • Autotuning PID control; also supports manual tuning and other control modes including alarm function
  • Stability to within 0.01°C easily obtained with a well-designed thermal system
  • Solid-state control utilizing an properly heatsinked solid-state relay for long-life and precise control
  • Burst fire switching: variable time-base proportioned switching for precise, reliable control and extended heater life
  • Maximum over-temperature protection utilizing an independent limit module
  • Open loop protection shuts down output if open loop operation is detected
  • Over-current protection using a front panel circuit breaker
  • Dual LED displays for simultaneous indication of process temperature and setpoint in Fahrenheit or Celsius; Percent duty cycle can also be displayed
  • Industrial rackmount enclosure with receptacles and removable cords
  • Display resolution: 0.1°C
  • Absolute accuracy: ±1°
  • Sampling rates:
    • Model 521 main controller: 10 Hz
    • Model 621 main controller 20 Hz
    • Limit controller: 10 Hz
  • Input/Output power:
    • 100 to 240 VAC, 50-60 Hz
    • 30A max heater current
    • 40mA minimum heater load (6000 ohms for 240VAC, 3000 ohms for 120VAC)
    • Standard NEMA L6-30 twist-lock connectors (other NEMA configurations available)
  • Ungrounded* thermocouple sensor inputs
    • range: thermocouple specific
    • ambient rejection: less than 0.10°C/°C
    • connector: mini and standard size
  • Pt-100 RTD (2 or 3 wire) sensor inputs
    • range: -128.8 to 537.7°C
    • ambient rejection: less than 0.05°C/°C
    • connector: 2 or 3-pin uncompensated "thermocouple style"
  • Communications: MODBUS message protocol over RS-232 or RS-485 (specify when ordering, optional on 521, standard on 621) through 9-pin female D-sub connector
  • Optional analog input and/or output: user-selectable 0-10V, 0-5V, 1-5V, 4-20mA, or 0-20mA through 9-pin female d-sub connector
  • Size: EAI 19" rackmount, 5.25"h x19"w x13"d (3 rack units high), 14 lbs.
  • Ambient temp range: 0 to 50°C, non-condensing

*If using thermocouple inputs, only ungrounded thermocouples are recommended for the control input. If a grounded thermocouple is required, the remote programming input must be isolated to prevent ground loops.

Standard configurations are equipped for only one sensor type: either an ungrounded thermocouple or a 100 Ohm platinum RTD. Please specify sensor type when ordering. Rare-element or special thermocouple configurations (type-R/S, B, or C) can be specified - allow extra time for delivery.

HomeGas AnalyzersTemperature ControllersAboutUsContact

Copyright 2004 © Brand-Gaus, LLC. All rights reserved.
Cedar Park, Texas
Tel: 512-506-9655
Privacy Policy   Terms and Conditions
Watlow is a registered trademark of
Watlow Electric Manufacturing Co.